IEC 60599:2022 Ratio Analysis

Three-ratio method for transformer fault classification in mineral oil

Gas Concentrations (ppm)

Hydrogen

Recommended range: 0 to 100 ppm

Methane

Recommended range: 0 to 120 ppm

Acetylene

Recommended range: 0 to 1 ppm

Ethylene

Recommended range: 0 to 50 ppm

Ethane

Recommended range: 0 to 65 ppm

Load sample data:

Zone Visualization

0.0050.0050.010.010.050.050.10.10.50.511551010PDT3T2T1D2D10.010.10.2R2 (CH₄/H₂)R1 (C₂H₂/C₂H₄)
PD
D1
D2
T1
T2
T3

Enter gas concentrations to see analysis results

About IEC 60599:2022

The IEC 60599 ratio method uses three gas ratios to classify transformer faults:

  • R1 = C₂H₂/C₂H₄ (Electrical vs thermal)
  • R2 = CH₄/H₂ (Fault temperature)
  • R3 = C₂H₄/C₂H₆ (Thermal refinement)

NS = Not Significant (ratio cannot be calculated due to low denominator gas)

About the IEC 60599:2022 Ratio Method

The IEC 60599:2022 standard provides guidance on the interpretation of dissolved and free gases in mineral oil-filled electrical equipment. The three-ratio method is one of the most widely used techniques for transformer fault diagnosis worldwide.

The Three Ratios

  • R1 = C₂H₂/C₂H₄(Acetylene/Ethylene) - Distinguishes electrical faults from thermal faults. High values indicate arcing.
  • R2 = CH₄/H₂(Methane/Hydrogen) - Indicates the relative temperature of the fault. Low values suggest partial discharges.
  • R3 = C₂H₄/C₂H₆(Ethylene/Ethane) - Refines thermal fault temperature classification. High values indicate higher temperatures.

Fault Types

CodeFault TypeTemperature RangeSeverity
PDPartial Discharges< 150°C (cold plasma)Medium
D1Discharges of Low EnergyVariable (arc)High
D2Discharges of High Energy> 3000°C (arc core)Critical
T1Thermal Fault< 300°CMedium
T2Thermal Fault300-700°CHigh
T3Thermal Fault> 700°CCritical

Important Notes

  • NS (Not Significant) - When a gas concentration is too low, the ratio cannot be reliably calculated.
  • DT (Diagnosis Tentative) - When ratios don't match any defined zone, multiple concurrent faults may be present.
  • This tool should be used in conjunction with other diagnostic methods such as the Duval Triangle and Pentagon.

References

  • IEC 60599:2022 - Mineral oil-filled electrical equipment in service
  • IEEE Std C57.104-2019 - Guide for the Interpretation of Gases Generated in Mineral Oil-Immersed Transformers